Choosing the right DC isolator switch is crucial for ensuring safety, reliability, and efficiency in solar power systems or other DC applications. A quality isolator...
More >>Protection: gS
Rated Voltage: DC80V
Rated Current: 4-1000A
Breaking Capacity: 25kA
TUV,CE Approve
Type |
Rated Voltage (V) |
Rated current (A) |
Overall dimension (mm) |
ATCT-00 |
80V |
4、6、10、16、20、25、32、40、50、63、80、100、125、160、 200、224、250、300、315、350、400、425、500、600A |
Draw 1 |
Type | Figure No. | Rated current (A) | Watts Loss (W) | Energy Integrals I²t(A²s) | Fuse Holder Type | Fuse Handle Type | |
Pre-Arcing I²t | Total l²t | ||||||
ATCT | 00 | 4 | 1.6 | 45 | 135 | Single weight: 195g ATCT-160 ATCT-250 |
NH/NT Handle |
6 | 1.8 | 65 | 165 | ||||
10 | 2.0 | 90 | 270 | ||||
16 | 3.0 | 240 | 490 | ||||
20 | 3.2 | 460 | 970 | ||||
25 | 3.4 | 890 | 1730 | ||||
32 | 4.0 | 1580 | 3050 | ||||
40 | 4.6 | 2600 | 4900 | ||||
50 | 5.1 | 3850 | 7100 | ||||
63 | 6.2 | 5600 | 10300 | ||||
80 | 6.8 | 8500 | 15700 | ||||
100 | 8.2 | 14900 | 25100 | ||||
125 | 9.1 | 25800 | 45800 | ||||
160 | 10.9 | 48000 | 79000 | ||||
ATCT | 00 | 200 | 12.5 | 89400 | 147000 | Single weight: 200g ATCT-250 |
NH/NT Handle |
224 | 13.2 | 138000 | 230000 | ||||
250 | 14.5 | 192000 | 310000 | Single weight: 210g ATCT-400 ATCT-600 |
NH/NT Handle | ||
300 | 17.5 | 293000 | 455000 | ||||
315 | 18.2 | 360000 | 549000 | ||||
355 | 19.5 | 434000 | 630000 | ||||
400 | 20.9 | 540000 | 755000 | ||||
425 | 21.5 | 620000 | 861000 | Single weight: 216g ATCT-600 |
NH/NT Handle | ||
500 | 24.3 | 880000 | 1200000 | ||||
600 | 28.9 | 125000 | 1690000 |
ATCT-00 TIME CURRENT CURVE
This series of fuses are applicable to the lines with DC rated voltage up to 80V and rated current up to 600A. They are used as short circuit and overload protection for equipment and devices of power distribution or communication circuit system such as conductor, power supply and communication cabinet. The rated breaking capacity is up to 25kA. It has the performance of miniaturization, large capacity, low power consumption and high current limit. The product meets the provisions of national standard GB / t13539.4 and International Electrotechnical Commission Standard iec60269-4.
If you have any questions or comments, we are ready to help. Please allow 24 hours of response time in working days
GET A QUOTE